Journal of Electrical and Computer Engineering / 2022 / Article / Tab 10 / Research Article
Security Enhancement of Power Systems through Interline Power Flow Controller (IPFC) under Contingency Condition: A Case Study and Analysis‐EEP 400 kV System Table 10 LSI during an outage of Sebeta to the Holeta branch with IPFC.
From To Actual MVA Rated MVA LUF (%) NLSI (%) LSI (%) GG3 W/Sodo 791.158 1973 40.099 15.007 32.572 W/Sodo GG2 166.666 1973 8.447 7.958 8.301 W/Sodo Gelan 540.544 1973 27.397 53.273 35.160 W/Sodo Yirgalem 134.246 1973 6.804 5.437 6.394 GG2 Sebeta 111.157 1341 8.289 7.751 8.128 GG2 GGnew 51.940 1341 3.873 0.533 2.871 Gelan Sebeta 745.080 1973 37.764 11.432 29.864 Gelan Holeta 186.858 1973 9.471 2.046 7.243 Gelan D/Zeit 313.985 1973 15.914 2.243 11.813 Sebeta Holeta 0.000 1973 0.000 0.000 0.000 Holeta Sululta 547.526 1973 27.751 3.198 20.385 Sululta D/Markos 156.883 1341 11.699 20.285 14.275 Sululta D/Zeit 306.821 1973 15.551 7.875 13.248 Sululta G/Gurcha 199.738 1341 14.895 8.369 12.937 D/Markos B/Dar 342.632 1341 25.550 22.809 24.728 D/Markos G/Gurcha 480.879 1341 35.860 9.807 28.044 B/Dar Beles 350.024 1341 26.102 8.808 20.914 Beles GERD 86.173 1973 4.368 7.007 5.159 Yirgalem GD3 130.894 1973 6.634 12.339 8.346