Journal of Electrical and Computer Engineering / 2022 / Article / Tab 2 / Research Article
Security Enhancement of Power Systems through Interline Power Flow Controller (IPFC) under Contingency Condition: A Case Study and Analysis‐EEP 400 kV System Table 2 Transmission line parameters of 400 kV system.
No From To R (pu) X (pu) B (pu) S (MVA) 1 GG3 W/Sodo 0.0010 0.0081 0.0004 1973 2 W/Sodo GG2 0.0025 0.0207 0.0010 1973 3 W/Sodo Gelan 0.0055 0.0432 0.0024 1973 4 W/Sodo Yirgalem 0.0024 0.0197 0.0009 1973 5 GG2 Sebeta 0.0028 0.0378 0.0013 1341 6 GG2 GGnew 0.0004 0.0057 0.0002 1341 7 Gelan Sebeta 0.0007 0.0057 0.0003 1973 8 Gelan Holeta 0.0010 0.0079 0.0004 1973 9 Gelan D/Zeit 0.0006 0.0049 0.0003 1973 10 Sebeta Holeta 0.0003 0.0034 0.0001 1973 11 Holeta Sululta 0.0006 0.0050 0.0003 1973 12 Sululta D/Markos 0.0033 0.0444 0.0015 1341 13 Sululta D/Zeit 0.0018 0.0137 0.0006 1973 14 Sululta G/Gurcha 0.0020 0.0271 0.0009 1341 15 D/Markos B/Dar 0.0030 0.0399 0.0014 1341 16 D/Markos G/Gurcha 0.0014 0.0180 0.0006 1341 17 B/Dar Beles 0.0010 0.0122 0.0005 1341 18 Beles GERD 0.0045 0.0460 0.0018 1973 19 Yirgalem GD3 0.0057 0.0444 0.0024 1973