Journal of Electrical and Computer Engineering / 2022 / Article / Tab 7 / Research Article
Security Enhancement of Power Systems through Interline Power Flow Controller (IPFC) under Contingency Condition: A Case Study and Analysis‐EEP 400 kV System Table 7 LSI during an outage of Sebeta to the Holeta branch without IPFC.
From To Actual MVA Rated MVA LUF (%) NLSI (%) LSI (%) GG3 W/Sodo 2132.794 1973 108.099 34.1900 85.926 W/Sodo GG2 1221.193 1973 61.8950 57.0110 60.430 W/Sodo Gelan 2025.377 1973 102.655 153.159 117.806 W/Sodo Yirgalem 171.2350 1973 8.67900 6.34400 7.979 GG2 Sebeta 140.7990 1341 10.5000 12.1800 11.004 GG2 GGnew 90.96300 1341 6.78300 0.8220 4.995 Gelan Sebeta 2061.160 1973 104.468 56.546 90.092 Gelan Holeta 2098.737 1973 106.373 87.336 100.662 Gelan D/Zeit 1289.108 1973 65.3370 42.359 58.444 Sebeta Holeta 0 1973 0 0 0 Holeta Sululta 831.8770 1973 42.1630 7.797 31.853 Sululta D/Markos 355.3140 1341 26.4960 25.254 26.124 Sululta D/Zeit 811.2700 1973 41.1190 25.938 36.564 Sululta G/Gurcha 208.0350 1341 15.5130 7.929 13.238 D/Markos B/Dar 390.3600 1341 29.1100 40.433 32.507 D/Markos G/Gurcha 559.0270 1341 41.6870 7.840 31.533 B/Dar Beles 357.8380 1341 26.6840 8.683 21.284 Beles GERD 97.15600 1973 4.92400 8.754 6.073 Yirgalem GD3 208.8480 1973 10.5850 18.631 12.999