Journal of Electrical and Computer Engineering / 2022 / Article / Tab 8 / Research Article
Security Enhancement of Power Systems through Interline Power Flow Controller (IPFC) under Contingency Condition: A Case Study and Analysis‐EEP 400 kV System Table 8 Bus voltage magnitude and phase angle with IPFC.
Buses Base case scenario N-1 case scenario No Name Vbus (pu) Ang (deg) Vbus (pu) Ang (deg) 1 GG3 1 0 1 0 2 W/Sodo 1.0099 −2.32586 1.047 −0.0868 3 GG2 0.9997 −1.50792 1 −0.1846 4 Gelan 0.9836 −10.3944 1 −0.3288 5 Sebeta 0.9839 −10.2937 1 −0.3104 6 Holeta 0.9863 −10.5381 0.985 −0.3333 7 Sululta 0.9923 −10.775 0.9804 −0.3359 8 D/Markos 1.0055 −9.50964 1.0047 −0.3541 9 B/Dar 0.9984 −4.40367 1.0161 −0.3839 10 Beles 0.9995 −1.81031 1 −0.3921 11 GERD 1.0001 −3.31649 0.9695 −0.3935 12 D/Zeit 0.9852 −10.7558 0.9687 −0.331 13 Yirgalem 1.0396 −1.19638 1.013 −0.091 14 GD3 1.0486 2.98491 1 −0.099 15 G/Gurcha 1.0114 −10.2523 0.977 −0.3471 16 GGnew 0.9998 −1.17979 1 −0.1883