Research Article
Planning and Design of Low-Power-Consuming Full-Outer-Air-Intake Natural Air-Conditioning System
Table 2
Comparison table of the building energy conversion system and traditional total heat exchanger system.
| | Item | This subjected system | Total heat exchanger | | Rotary wheel | Polymer fixed plate |
| | Energy conversion method | Air and water | Air | Air | | Fan power | Variable air volume | Constant air volume | Constant air volume | | Equipment power | Fan and pump | Wheel motor and fan | Fan | | Separation of intake/exhaust air | Entirely separated | Mixed up | Separated by highly permeable fibers | | Air cross-contamination | No | Yes | Yes | | Positive/negative environment | Yes | No | No | | Sensible energy conversion efficiency | 71%∼112% | 65%∼78% | 65%∼78% | | EER | 24.87∼13.69 kcal/W·h | N/A | 5.43∼0.07 kcal/W·h |
|
|
N/A: unable to measure EER because the wheel-type total heat exchanger does not provide a similar model.
|