Planning and Design of a Full-Outer-Air-Intake Natural Air-Conditioning System for Medical Negative Pressure Isolation Wards

Table 1

Air exchange rate per hour (ACH) and the time (in minutes) required for airborne contaminants’ removal with the efficiency of 90%, 99%, and 99.9%, respectively [35].

Air exchange rate per hour (N)Minutes required for airborne contaminants’ removal corresponding to different efficiencies
90%99%99.9%

1138276414
269138207
34692138
43569104
5285583
6234669
7203959
8173552
9153146
10142841
11132538
12122335
13112132
14102030
1591828
1691726
1781624
1881523
1971522
2071421
2561117
305914
354812
403710
45369
50368