Planning and Design of a Full-Outer-Air-Intake Natural Air-Conditioning System for Medical Negative Pressure Isolation Wards
Table 7
Performance and function comparison of the proposed full-outer-air-intake negative pressure ward and that of traditional technology.
| | Item | Proposed full-outer-air-intake negative pressure ward | Traditional negative pressure ward |
| | Introduce fresh outer air | Yes | No | | Air cross-contamination | No | Yes | | CO2 concentration control | Yes | No | | Exhaust air volume control | Yes | No | | Sensible heat exchange efficiency (ηs) | 105.88% | No | | Air change rate (N) | Max. 54.4 times Min. 40 times | ≧12 times |
|
|