Research Article

[Retracted] On the Performance and Efficiency of Surface Air Cooler Working under High Temperature and High Humidity Condition

Table 3

Comparison of surface coolers in different applications.

Types of surface cooler applicationThe head-on wind speed (m/s)Air humidity ratio after dehumidification by surface cooler (g/kg dry air)The heat exchanger efficiency of the cooler ηao

Surface cooler for chiller units used in conventional air-conditioning [3]1.89.50.694
Surface cooler for evaporative chiller units used in hot and humid areas [5]1.812.70.617
Surface cooler for dehumidifying high temperature and high humidity air in wastewater recovery treatment [16]2.016.440.525
Surface air cooler in this paper1.812.680.621
0.57.450.867