Research on the Three-Dimensional Power Frequency Electric Field Measurement System
Table 3
Sensor consistency test and calibration data.
| Input voltage (kV) | Electric field strength (kV/m) | Sensor 1 output (mV) | Sensor 2 output (mV) | Sensor 3 output (mV) | Sensor 4 output (mV) | Sensor 5 output (mV) | Sensor 6 output (mV) |
| 0.1 | 0.33 | 30 | 21 | 44 | 35 | 38 | 46 | 5 | 16.67 | 332 | 308 | 355 | 338 | 340 | 343 | 10.5 | 35 | 700 | 723 | 711 | 695 | 688 | 703 | 15.4 | 51.33 | 1020 | 1025 | 1013 | 1036 | 1037 | 1041 | 20.3 | 67.67 | 1340 | 1311 | 1322 | 1369 | 1323 | 1322 | 25.2 | 84 | 1640 | 1634 | 1611 | 1665 | 1618 | 1641 | 29.6 | 98.67 | 1920 | 1894 | 1890 | 1929 | 1918 | 1925 | 35.1 | 117 | 2260 | 2289 | 2265 | 2251 | 2249 | 2232 | 40 | 133.33 | 2550 | 2540 | 2572 | 2543 | 2517 | 2600 | 44.9 | 149.67 | 2850 | 2880 | 2860 | 2808 | 2897 | 2829 | 50.5 | 168.33 | 3170 | 3143 | 3189 | 3128 | 3175 | 3133 | 60.1 | 200.33 | 3802 | 3828 | 3784 | 3810 | 3817 | 3773 |
|
|
Analysis of the above experimental results.
|