Research Article

Partial Least Squares (PLS) Integrated Fourier Transform Infrared (FTIR) Approach for Prediction of Moisture in Transformer Oil and Lubricating Oil

Table 6

Self-prediction of the calibration samples (transformer oil).

Expected moisture content (ppm)Predicted concentration (ppm)

0137 ± 202
500422 ± 317
700866 ± 382
10001394 ± 264
20002250 ± 715
30002622 ± 416
40003782 ± 159
50004789 ± 359