[Retracted] Construction of Grid Reliability Assessment Model Based on Sensitivity Analysis
Table 1
Common indicators of IEEE 1366-2012 and DL/T 836-2016.
Indicator type
Indicator name
Nonidentical part
System user index
Average supply reliability (ASAD)
IEEE1366-2012: Only continuous outages (outage time greater than 5 min) are considered
DLT836-2016
(1) Considering both continuous outage (outage time greater than 3 min) and short-time outage
(2) Further refined into 4 indicators according to whether to take into account external influence, system power shortage limitation, and short-time power outage
System average outage duration (SAID) System average outage frequency (SAIED)
IEEE1366-2012: Only continuous outages are considered
DLT836-2016
(1) Considering both continuous outage and short-time outage (2) Further refined into 6 indicators according to whether to take into account external influence, system power shortage limitation, and short-time outage, as well as separate statistics for prearranged outage and fault outage
Outage user index
Average outage customer outage time (CAIDD) Average time per outage (CTADI) Average outage frequency for customers with power outages (CAIFD)
IEEE1366-2012: Only continuous outages are considered
DLT836-2016
(1) Considering both continuous outage and short-term outage
(2) Further refined into 2 indicators according to whether short-time outages are taken into account
Long-time outage index
Ratio of customers with a prolonged power outage
Ratio of single long-time outage customers
Repeat outage indicators
Ratio of customers with multiple outages Ratio of customers with multiple persistent outages
Load-based metrics
Average system equivalent downtime (ASIDI)
Average system equivalent outage frequency (ASIFI)
Short-term outage indicators
System average short-time outage frequency (MAIFI)
DLT836-2016: 2 additional indicators based on separate statistics for prearranged outages and fault outages