[Retracted] Construction of Grid Reliability Assessment Model Based on Sensitivity Analysis

Table 1

Common indicators of IEEE 1366-2012 and DL/T 836-2016.

Indicator typeIndicator nameNonidentical part

System user indexAverage supply reliability (ASAD)IEEE1366-2012: Only continuous outages (outage time greater than 5 min) are considered
DLT836-2016
(1) Considering both continuous outage (outage time greater than 3 min) and short-time outage
(2) Further refined into 4 indicators according to whether to take into account external influence, system power shortage limitation, and short-time power outage
System average outage duration (SAID)
System average outage frequency (SAIED)
IEEE1366-2012: Only continuous outages are considered
DLT836-2016
(1) Considering both continuous outage and short-time outage
(2) Further refined into 6 indicators according to whether to take into account external influence, system power shortage limitation, and short-time outage, as well as separate statistics for prearranged outage and fault outage
Outage user indexAverage outage customer outage time (CAIDD)
Average time per outage (CTADI)
Average outage frequency for customers with power outages (CAIFD)
IEEE1366-2012: Only continuous outages are considered
DLT836-2016
(1) Considering both continuous outage and short-term outage
(2) Further refined into 2 indicators according to whether short-time outages are taken into account
Long-time outage indexRatio of customers with a prolonged power outage
Ratio of single long-time outage customers
Repeat outage indicatorsRatio of customers with multiple outages
Ratio of customers with multiple persistent outages
Load-based metricsAverage system equivalent downtime (ASIDI)
Average system equivalent outage frequency (ASIFI)
Short-term outage indicatorsSystem average short-time outage frequency (MAIFI)DLT836-2016: 2 additional indicators based on separate statistics for prearranged outages and fault outages