Abstract

Axial fans play a pivotal role in the road tunnel ventilation system. Qualified performance of the axial fan is important for both safety and air quality maintenance reasons. Axial fans performance in situ test of Qinling Zhongnan Mountain highway tunnel, the second longest road tunnel in the world, is presented in this research. Performance test items and the qualification criterion, as well as a general framework for the road tunnel axial fan assessment, are recommended. Log-Tchebycheff method is suggested to confirm the location for the measuring lines and points. The precision of the log-Tchebycheff method in air flow rate measuring is verified by comparing with the biharmonic spline interpolation fitting result. The research shows that the log-Tchebycheff method has high precision and good efficiency in the air flow rate measurement of the road tunnel air duct. What is more, the biharmonic spline interpolation fitting method can be applied to obtain a more accurate result. The number of interpolation points of the biharmonic spline interpolation fitting method should be bigger than 2000 to provide quality results.

1. Introduction

Ventilation plays a critical role in both normal operating [1] and fire [2, 3] situations of a tunnel. It should keep the air pollutant such as , , and smoke dust in low concentration, prevent the smoke back layering, and exhaust smoke [46] out of the tunnel. Especially, long tunnels necessitate a fine-tuned control of the ventilation system for safety and air quality maintenance reasons [7, 8]. Axial fans and jet fans constitute the main part of the tunnel ventilation system. Indoor or numerical researches on jet fans preference are extensively established [915]. For axial fans, it is generally diagnosed by comparing the fan performance curve provided by the fan manufacturer with the required performance parameters of the designed tunnel. Usually, the fan performance curve provided by the manufacturer is obtained from their laboratory test. However, there exists a great difference between the laboratory performance curve and the in situ one for reasons such as the fan misalignment, operating environment diversity, and added structures (including diffusion tube, collector, muffler, etc.). On the other hand, the ageing of the axial fan could also bring a reduction to its performance. The average efficiency of fans is only 57% [16] at present and most of them service far different from their designed working point. Thus, an in situ test is urgently needed to determine whether the axial fan is still sufficient at the designed point when to be installed in the real tunnel fan room environment as well as with time ageing.

To date, the axial fan in situ test has gained much attention in the mine ventilation [1721], but little attention has been given to the road tunnels. It takes granted that research fruits such as mine fan static pressure and motor parameters tests can be used for reference in the tunnel axial fan in situ test. However, first and foremost, air flow rate measurement during the performance test of the tunnel fans is much more difficult than mine fans. The cross-section area of the tunnel air duct is usually two to three times than that of the mine air duct and is always much shorter. For these reasons, the wind field of road tunnel air duct is more disordered which brings difficulty to the precision measurement of the air flow rate.

The air flow rate in a section of tunnel or air duct may be determined in two ways: either by measuring the pressure difference produced by a differential pressure device (orifice plate, venturi tube, nozzle, or pitot tube) or by determining the velocity at various points in this section and then calculating the mean velocity. The pressure difference method is divided into dynamic and static methods. Two cross sections with different areas and static air flows, which are always difficult to select, are required in the static pressure difference method. Similarly, the dynamic difference method requires a large number of pitot tubes, which always produces an air leak problem. In addition, a conversion between the test result and air velocity is needed before we can obtain the air flow rate with these two methods. In contrast, the air velocity method can provide the air flow rate directly and is extensively applied in fan performance in situ tests.

Air velocity method has been used and developed by researches in different fields. Single point measurement is the most common method used in air flow rate tests [22]. Only a single point of air velocity was tested and treated as the average velocity of each test section among these studies. Considering the inaccuracy of single point measurements, Qiu et al. [23] divided the test section into several parts in their study on the friction coefficient of a shot concrete lining. The air velocity at the centroid of each small part was measured, and their arithmetic mean was regarded as the mean air velocity of the section. Similar method was performed by Wang et al. [24, 25], Fang et al. [26], and Ren et al. [27] during the ventilation performance testing of a complementary ventilation tunnel. Compared with the single point measurement, these multipoint experiments were more accurate. However, the data for every point were not measured at the same time [28]. To obtain all of the multipoint measurement data simultaneously, Yang et al. [29] investigated a tunnel’s ventilation performance via several wind cups. A tunnel section was also divided into equal area parts, and a steel frame for supporting the wind cup was used in this experiment. All the air velocities could be measured at the same time. A five-point truss was utilised by Levoni et al. [28] to investigate the fluid dynamic characterisation of the Mont Blanc tunnel. These simultaneous multipoint velocity measurements constitute the available method for collecting reliable mean air velocity data along a tunnel’s cross section and estimating the total flow rate.

This is because the influence of the tunnel walls and disordered distribution of the air velocity along its cross section make direct measurements of the air flow rate a very difficult task. Usually, the flow velocity is zero at the tunnel lining wall and reaches its maximum at the centre of the cross section. The velocity distribution between the tunnel wall and cross-section centre changes with the flow condition of the air [30]. The weights of the measuring points in the above methods are all equal. Therefore, the velocity change along the tunnel section is ignored in these methods. Thus, a simultaneous multipoint air flow measurement method that considers the air distribution of the tunnel cross section is urgently needed.

To have road tunnel axial fans assessed, this work firstly presents the performance test items and qualification criterion for road tunnel axial fans. Then, combined with the in situ test of Qinling Zhongnan Mountain highway tunnel, the general process of an axial fan assessment is stimulated. What is more, thought a theoretical analysis, the log-Tchebycheff method is suggested to confirm locations for measuring lines and points. Its precision in air flow rate measuring is verified by comparing with the MATLAB fitting results. Finally, the performance of the axial fan of the tunnel is assessed via performance curves established by the in situ result.

2. Engineering Background

The Qinling Zhongnan Mountain highway tunnel is 18020 m long, making it the longest tunnel in Asia and the second longest road tunnel in the world. A three-shaft ventilation system is used for the Qinling Zhongnan Mountain highway tunnel (Figure 1). A total of 32 high-power axial fans were installed in the three ventilation shafts. Shaft 1 has nine fans: four exhaust fans and five inlet fans. Shaft 2 has 12 fans: six exhaust fans and six inlet fans. Shaft 3 has 11 fans: five exhaust fans and six inlet fans. The inlet fans were made by the South Fan Company of China. The exhaust fans were made by the Flack Woods Company in the UK.

The detailed structure of the shaft 1 is shown in Figure 2. The axial fans are located in an excavated underground fan room (red circles in Figure 2). Denote that the drive direction of the left line of the main tunnel is from An Kang to Xi’an. The drive direction of the right line is from Xi’an to An Kang. As can be seen from Figure 2, the direction of the air flow of both left and right lines is the same as the drive direction. In this way, the pressure caused by the traffic flow can be used as an impetus rather than a resistance of the tunnel ventilation. The air flow direction is quite clear by applying the three shafts in this tunnel. The polluted air will be firstly discharged by the exhaust fans via the air output duct. Then, the fresh air will be brought into next section of the main tunnel by inlet fans via the air inlet duct (yellow arrows in Figure 2).

3. Assessment Criteria and Test Items

3.1. Assessment Criteria

For road tunnels, four items are recommended here to verify an eligible axial fan:

3.1.1. Maximum Air Flow Volume

Tunnel ventilation axial fans must provide sufficient volume of fresh air to keep the tunnel operating environment qualified in its CO concentration and visibility. Thus, the maximum volume of an axial air flow rate should be greater than the required fresh air volume.

3.1.2. Difference between the Tested Total Pressure and Designed Total Pressure at the Designed Operating Point

To ensure the newly installed or service fans work as it designed and keep its performance, the difference between the tested total pressure and designed total pressure should be limited within 5%.

3.1.3. Fan Motor Capacity Safety Factor

The fan motor must have sufficient motivation to maintain the fan’s operation, pony cart is not allowed here. The highway tunnel design code of China [31] has stipulated that the fan motor capacity safety factor should be bigger than 1.1.

3.1.4. Total Pressure Efficiency at the Designed Operating Point

The daily electricity consumption of the operation of Qinling Zhongnan Mountain highway tunnel is 12652 kW·h (equivalent to 1890 US dollars). The ventilation costs account for more than 70% [31] of the total electricity consumption. Thus, the high efficiency of the axial fan is significant to the energy-saving operation of tunnels. The recommended lower limit of fan total pressure efficiency is 70%[31].

3.2. In Situ Items and Methods

The fan performance curves consist of volume, total pressure curve; volume, axial power curve; and volume, efficiency curve. Take Qinling Zhongnan Mountain highway tunnel as an example, to obtain the most reliable test data, the ventilation network during the in situ test was the same as that used during its daily operation. As shown in Figure 3, air from the main tunnel was firstly discharged into the air inlet duct and then travelled across the axial fan. Finally, it was blown into the shaft via the air outlet duct. The calculation process of the fan air flow rate, fan total pressure, axial power, efficiency and fan motor capacity safety factor will be presented in detail in the flowing sections.

3.2.1. Fan Air Flow Rate

As shown in Figure 3, the air flow rate of the fan at the cross section 3-3 was difficult to be measured. Fortunately, the air flow rate at 4-4 was easy to be measured. The mass flow rate at each section of the duct is the same. Thus, the air flow rate measurement section was chosen as the cross section 4-4. Once the mass flow rate of the duct could be determined, the volume flow rate of the fan (section 3-3) could then be obtained.

The relationship between the mass flow rate and the volume flow rate can be presented as follows:where is the mass flow rate, is the total volume flow rate of the cross section 4-4 which can be determined by the air flow rate measurement, is the air density of the cross section 4-4 which can be determined by using the following equation:where is the air density of the cross section i-i (kg/m3), is the absolute static pressure of the cross section i-i (Pa), is the relative humidity (%), t is the temperature (°C), and is the air absolute saturated steam pressure at temperature t in Pa.

The precise measurement of the total volume flow rate ( for section 4-4) was the most difficult work in this in situ test. The velocity-area method has been proven to be one of the most accurate methods for the air flow rate measurement. However, the position of measurement points has great influence on the accuracy of test results. Previous research [32] showed that the log-Tchebycheff method could provide more accurate test results than the equal area method. Thus, the log-Tchebycheff method was recommended in this work. The air velocity in the tunnel is not homogeneous along its cross section. The air velocity distribution is disordered and difficult to regulate. Thus, it is necessary to divide the cross section into many parts. If each part is small enough, the velocity of this small part could be treated as a constant. Then, the total flow rate could be represented by the following equation:where indicates the air flow rate of the tunnel cross section i-i, is the area of the ith part, and is the velocity of the ith part.

Considering the air in the tunnel to be a fully developed turbulent flow, the boundary condition at the tunnel surface can be expressed as follows:The boundary condition at the centre of the section is as follows:where is the axial velocity of a point of the tunnel cross section, is the distance between the point and the tunnel wall surface, R is the hydraulic radius of the tunnel, and the dimension of velocity gradient is (s−1).

The velocity model should be considered in two parts. The first part is the velocity distribution of the zone near the wall. The velocity distribution of this part is in line with the following properties:where v+ is the dimensionless flow velocity, , indicates the shear stress velocity, , is the shear stress, is the air density, is the dimensionless distance to the tunnel surface, and and are constant.

The second part is the zone away from the tunnel wall. The velocity distribution of this part is in line with the following polynomial [33]:where are constant, is the number of measuring points in the same radius, and is the distance to the tunnel centre.

Taking into account the wind tunnel airflow distribution, the true function of the flow rate distribution on the two parts could be approximately expressed by Tchebycheff polynomials , . If we let , and can be expanded into the following cosine series:The th order Tchebycheff polynomial [34] is expressed as When , (9) can be reexpressed as follows:Let ; the Tchebycheff nodes can be expressed as follows:The nodes can be transferred from to any common situation by using the following equation:Thus, the new interpolation nodes can be calculated as follows: Locations of measure points in the rectangular section determined by the log-Tchebycheff method are shown in Figure 4, and the specific coordinates are listed in Table 1. The mean velocity can be calculated by the following considering an equal weight for each measuring point:where is the measured velocity of section i-i, e is the column number of the measuring point parallel to the short side of the rectangle, and f is the column number of the measuring point parallel to the long side of the rectangle.

The cross section of the tunnel was measured using a laser profiler before the determination of the location of measure points. Take section 4-4 as an example, its size and shape are shown in Figure 5 after the measurement by the laser profiler. An improved log-Tchebycheff method was then used because that the cross section was not a rectangle. This means a weight in line with the length of the measurement line was considered when calculating the air flow rate of the tunnel section. To achieve high precision, adjustments to the position of the measurement line of two adjacent wall edge regions had to be made. Specifically, if six measurement lines were used in the in situ test, then and , and if seven were used, then and (ISO 5802: 2001,1DT). The position of the middle lines can be checked in Table 2.

The measuring point distribution based on the log-Tchebycheff method is shown in Figure 5. Measuring lines 1 to 6 are shown from left to right, and the specific values are listed in Table 2. The TF-3 ventilator comprehensive tester applied in this test is shown in Figure 6.

The volume flow rate of the entire air duct can be expressed as follows:where is the total volume flow of section 4-4, is the arithmetic average velocity at the measuring point of the Nth measuring line, is the length of the Nth measuring line, and is the total number of measuring lines. is the length of the baseline between the tunnel surfaces.

The axial fan air flow rate can be then calculated as follows:where is the axial fan flow rate.

3.2.2. Fan Total Pressure

The total pressure of the axial fan can be expressed as follows:where is the axial fan total pressure, is the total pressure of section i-i, and is the pressure loss caused by the fan collector and diffusion tube.

In (17),where is the absolute static pressure of section i-i and can be calculated by (19) and can be expressed by (20) and (21).In (20) and (21), and are the areas of sections 2-2 and 3-3, respectively. In (19), is the relative static pressure which can be determined by the U-shaped manometer:

As shown in Figure 7, four hydrostatic test holes were made in sections 2-2 and 3-3. These were connected to a single pressure transmission pipe, which was then connected to a U-shaped manometer. The result shown by the U-shaped manometer was the relative static pressure of the inlet and outlet of the fan.

The value of can be expressed as follows:where is the collector tapered loss coefficient, is the diffusion tube expansion loss coefficient, and is the fan inlet velocity and can be calculated as follows:where is the area of the fan inlet.

3.2.3. Total Pressure Efficiency

The fan axial power can be expressed as follows:where is the fan axial power, is the motor efficiency based on the Chinese code of Guidelines for the Design of Ventilation of Highway Tunnels (JTG/T D70/2-02-2014)[31], the range of is 90%–95% ( = 93% is used in the following calculation), is the mechanical transmission efficiency between the motor and fan ( = 100%), and P1 is the motor input power that can be measured by the DJYC motor economy tester with the measurement precision of level 1. Because the motor power supply voltage of the fan was 6 kV, which was higher than the direct measurement limit of the tester. A voltage transformer (PT) and current transformer (CT) were used for the indirect measurement.

Based on the measured fan axial power and the fan output power, which could be calculated using the fan flow rate and fan pressure, the fan total pressure efficiency can be expressed by where is the fan output total pressure power.

3.2.4. Fan Motor Capacity Safety Factor

The axial fan motor capacity safety factor can be calculated by using the following equation:where is the axial fan motor capacity safety factor.

3.2.5. Standard Conditions Convention

In order to compare the performance of different types of axial fans, the test data calculation had to be converted to the situation with the rated fan rotational velocity and standard air state (with an atmospheric pressure of 101325 Pa, an air temperature of 20°C, a relative humidity of 50%, and an air density of 1.2 kg/m3) in accordance with the law of similarity.

The following equations can be applied to transfer the calculated parameters into the rated fan rotational velocity and standard air state:where is the converted air flow rate, is the converted fan total pressure, is the converted fan static pressure, is converted fan shaft power, is the converted fan output total pressure power, is the converted fan output static pressure power, is the air density conversion factor, is the rotational speed conversion factor, and and can be expressed as follows:where is the rated speed of the axial fan and is the measured speed of the axial fan.

4. General Steps for Tunnel Axial Fan Assessment

A general framework with six steps for a tunnel axial fan assessment is recommended in Figure 8. The first two steps which are finished via the in situ test are followed by the calculation processes in steps 3, 4, and 5. Usually, seven to ten different operating points should be tested for the fitting of one performance curve. Then, a “YES” or “NO” can be obtained in step 6 by comparing the result from step 5 with the tunnel axial fan assessment criteria. If the fan is not eligible, more detailed electric tests should be carried out to check the problem of the fan and then have it fixed. Another performance in situ experiment should be carried out to test the fixed axial fan after the repairing.

5. Test Results and Discussion

5.1. Precision of the Log-Tchebycheff Method

The calculation of the fan flow rate by using log-Tchebycheff method is free from the multiple integral. Thus, the air flow rate can be easily determined. The air of the tunnel is treated as a fully developed turbulent flow when using the log-Tchebycheff method. However, the actual distribution of air flow in the tunnel differs from the ideal turbulent flow distribution. Another method to get a more accurate air flow rate is by fitting the flow field through the measured flow speed data and then calculates the volume enclosed by the 3D fitting surface and its projection plane. Biharmonic spline [35] interpolation method can be applied to solve this 3D interpolation problem.

The fitted flow field is shown in Figure 9. Taking the duct with direction as the x-axis and the duct height direction as the y-axis, the air flow rate is shown in the z-axis. The volume enclosed by the 3D fitting surface and its projection plane can be expressed as follows:Seven sets of experiments at the different operating point were carried out to get performance curves of the axial fan. Take the first set of experiments as an example; the calculated air flow rate influenced by the interpolation points number is shown in Figure 9. It can be obtained from Figure 9 that the smooth of the fitting surface enhanced with the increase of the interpolation points number from 20 to 500. It is obvious that the more interpolation points we take, the more precise of the integral result will be. More detailed from Figure 10, the air flow rate rises sharply before its peak at 300 and then declines smoothly. When reaches to 2000, the calculation result tends to be stable. Thus, 2000 was chosen to be the number of interpolation points in the following calculations.

Comparison of the air flow rate results from the log-Tchebycheff method and MATLAB fitting are shown in Table 3, the difference between the two methods is about 4%. The log-Tchebycheff method showed high precision and great efficiency.

5.2. Fan Performance Assessment

According to the road tunnel axial fan assessment framework in Figure 8, curves are fitted in Figures 1113 based on the in situ test data. Now we assess the axial fan along the assessment criteria in section 2.2.

5.2.1. The Maximum Air Flow Rate

The maximum air flow rate of the tested fan is 157 m3/s. It is bigger than the designed operating point of 144 m3/s.

5.2.2. Difference between Tested Total Pressure and the Designed Total Pressure at Designed Operating Point

The tested total pressure at the designed operating point is 614 Pa (Figure 11). The difference is 2.5% when compared with the designed total pressure (630 Pa). It is smaller than the threshold of 5%.

5.2.3. Fan Motor Capacity Safety Factor

The in situ fan axial power at the designed operating point is 108.2 kW (Figure 12). The calculated fan motor capacity safety factor via (26) is 1.22 which satisfies the criteria.

5.2.4. Total Pressure Efficiency at the Designed Operating Point

It can be obtained from Figure 13 that the fan efficiency at the field environment is 78.6% which is more than 70%.

The assessment results of all the four items are “YES”. Therefore, the tested axial fan of Qinling Zhongnan Mountain highway tunnel is qualified.

6. Conclusion

An in situ experiment to exam the axial fan performance of Qinling Zhongnan Mountain highway tunnels was carried out. Assessment criteria, test items, and methods for a qualified tunnel ventilation axial fan were recommended. A general framework for the road tunnel axial fan assessment was also provided. The log-Tchebycheff method to determine the location of the air flow rate measurement points was proposed of which the precision was proven by comparing with the MATLAB fitting. Based on the investigations, the following conclusions are drawn:(1)Axial fan assessment is an essential work for the safety and efficiency operating of the road tunnel ventilation system.(2)The log-Tchebycheff method has qualified precision and good efficiency in measuring the air flow rate of a road tunnel.(3)The 3D surface fitting of which the number of the interpolation point is recommended to be bigger than 2000 can be applied to obtain a more accurate result of the air flow rate.

Data Availability

The data used to support the findings of this study are included within the article.

Conflicts of Interest

The authors declare that they have no conflicts of interest.

Acknowledgments

The research work reported herein was made possible by the Ministry of Transport of the People’s Republic of China (Grants no. 2013 318 802 400), Chang’an University (Grants no. 2008Z05), and Henan Provincial Department of Transportation (Grants no. 2017Z4). The financial support is highly appreciated.