Small-Signal Stability Analysis for Power System Frequency Regulation with Renewable Energy Participation

Table 1

Eigenvalues of the system.

CaseCharacteristic rootFluctuating frequency (Hz)Damping ratioRelevant units

Without wind or PV−0.9789 ± j6.87841.09470.1408G1, G2
−1.2415 ± j7.48951.23320.1582G1, G3
−0.3021 ± j4.12980.65730.0730G1, G5
−0.8243 ± j7.17761.00650.1292G1, G8
−0.5194 ± j7.98440.94760.0869G1, G9
−0.4123 ± j4.47770.79370.0824G1, G10
−0.6512 ± j6.67440.81560.1260G2, G3
−1.1654 ± j6.27320.74020.2430G2, G4
−0.9426 ± j5.00381.11160.1337G2, G5

Only wind−1.1584 ± j7.17771.14230.1593G1, G2
−1.3828 ± j7.98441.27070.1706G1, G3
−0.5108 ± j4.47780.71260.1133G1, G5
−1.0342 ± j6.67441.06220.1531G1, G8
−0.7109 ± j6.27320.99840.1126G1, G9
−0.4223 ± j5.00380.79630.0841G1, G10
−0.6718 ± j5.15940.82110.1291G2, G3
−1.2612 ± j4.81120.76570.2535G2, G4
−1.1018 ± j7.24961.15380.1502G2, G5
−0.4291 ± j0.79620.12670.4744G1-G10, DFIG

Only PV−1.3548 ± j7.50491.19440.1776G1, G2
−1.5051 ± j8.18821.30310.1807G1, G3
−0.7568 ± j4.88780.77790.1530G1, G5
−1.2497 ± j7.03361.11940.1749G1, G8
−1.0015 ± j6.75751.07550.1466G1, G9
−0.5817 ± j5.26950.83860.1097G1, G10
−0.7693 ± j5.32200.84700.1431G2, G3
−1.2929 ± j4.86400.77410.2569G2, G4
−1.2851 ± j7.55511.20240.1677G2, G5
−0.6627 ± j1.18560.18860.4879G1-G10, PV

Combination of wind and PV−1.4818 ± j7.71661.22810.1885G1, G2
−1.5323 ± j8.23361.31040.1829G1, G3
−0.8368 ± j5.02100.79910.1643G1, G5
−1.2958 ± j7.11051.13160.1792G1, G8
−1.0858 ± j6.89811.09780.1554G1, G9
−0.7138 ± j5.48950.87360.1289G1, G10
−0.9275 ± j5.58550.88890.1638G2, G3
−1.4302 ± j5.09270.81050.2703G2, G4
−1.5478 ± j7.99281.27210.1901G2, G5
−0.8182 ± j1.44460.22990.4928G1-G10, DFIG
−0.7283 ± j5.06650.80640.1423G1-G10, PV