Small-Signal Stability Analysis for Power System Frequency Regulation with Renewable Energy Participation

Table 2

IAE indices of six parameters acquired in two fault locations (in p.u.).

Cases: bus #3 voltage drop

Without wind or PV1.1551.239 × 0.7850.0940.5450.759
Only wind0.9561.058 × 0.6960.0890.5160.694
Only PV0.9111.042 × 0.6770.0870.5050.696
PV with energy storage system0.8701.024 × 0.6510.0830.4890.675
PV followed by wind0.8100.985 × 0.5940.0810.4700.648
Combination of wind and PV0.7150.898 × 0.4520.0760.4410.617

Cases: bus #15 voltage drop
Without wind or PV1.1961.314 × 0.8180.0980.5590.776
Only wind0.9281.082 × 0.7340.0950.5420.746
Only PV0.8971.066 × 0.6950.0920.5240.714
PV with energy storage system0.8461.034 × 0.6690.0880.5160.701
PV followed by wind0.7970.997 × 0.6190.0860.4900.692
Combination of wind and PV0.7310.921 × 0.4810.0780.4450.658