Research Article

Optimal Fractional Order Based on Fuzzy Control Scheme for Wind Farm Voltage Control with Reactive Power Compensation

Table 1

Protection type.

Protection typeLimitsDuration (s)

Instantaneous AC overcurrent1.2 pu
AC overcurrent (positive-sequence)1.15
AC current unbalance0.40.2
AC undervoltage (positive-sequence)0.951.5
AC overvoltage (positive-sequence)1.051.5
AC voltage unbalance (negative-sequence)0.050.2
AC voltage unbalance (zero-sequence)0.050.2
DC overvoltage1600 (V)0.001
Under/over frequency (Hz)[49.8, 50.2]2
Under speed/over speed (pu)[0.3, 1.5]5
Under/over wind speed (m/s)[4, 14]