Research Article
Optimal Fractional Order Based on Fuzzy Control Scheme for Wind Farm Voltage Control with Reactive Power Compensation
| Protection type | Limits | Duration (s) |
| Instantaneous AC overcurrent | 1.2 pu | | AC overcurrent (positive-sequence) | 1.1 | 5 | AC current unbalance | 0.4 | 0.2 | AC undervoltage (positive-sequence) | 0.95 | 1.5 | AC overvoltage (positive-sequence) | 1.05 | 1.5 | AC voltage unbalance (negative-sequence) | 0.05 | 0.2 | AC voltage unbalance (zero-sequence) | 0.05 | 0.2 | DC overvoltage | 1600 (V) | 0.001 | Under/over frequency (Hz) | [49.8, 50.2] | 2 | Under speed/over speed (pu) | [0.3, 1.5] | 5 | Under/over wind speed (m/s) | [4, 14] | |
|
|