Heat Transfer Simulation and Temperature Rapid Prediction for Trench Laying Cable

Table 3

Cable maximum temperature and electromagnetic loss with different computational grids (Tsur = 293.15 K, I = 800 A, and f = 50 Hz).

Cable modelGridRegionMaximum grid size (m)Minimum grid size (m)Total element numberTmax (K)Φloss (W)

Flat-type trench laying cableGrid 1Zone 10.00970.002410,881336.520190.65
Zone 20.29710.0049
Zone 30.31920.0199
Zone 43.10440.2489
Grid 2Zone 10.00570.001718,070333.742183.38
Zone 20.11370.0049
Zone 30.18150.0181
Zone 42.18440.1411
Grid 3Zone 10.00430.001527,610333.708182.55
Zone 20.09380.0042
Zone 30.15150.0117
Zone 41.83060.1117
Grid 4Zone 10.00240.001350,188333.541182.25
Zone 20.06820.0020
Zone 30.12560.0117
Zone 40.99780.0951

Trefoil-type trench laying cableGrid 1Zone 10.00600.001514,408342.287190.67
Zone 20.11400.0013
Zone 30.18150.0260
Zone 42.51120.1411
Grid 2Zone 10.00590.001522,618343.014189.69
Zone 20.09110.0012
Zone 30.14570.0227
Zone 41.78100.1088
Grid 3Zone 10.00470.001127,798341.779188.69
Zone 20.08850.0012
Zone 30.11730.0127
Zone 40.98680.1031
Grid 4Zone 10.00330.001153,290341.411188.71
Zone 20.08770.0011
Zone 30.10930.0103
Zone 40.48720.0748