Lightning Protection Improvement and Economic Evaluation of Thailand’s 24 kV Distribution Line Based on Difference in Grounding Distance of Overhead Ground Wire

Table 2

Parameters in ATP-EMTP modeling.

DescriptionData

Lightning currentPeak value40 kA
Time to half value77.5 μs
Time to crest value0.936/0.411 = 4.12 μs

Conductor (single)Outside diameter16 mm
Direct current resistance0.2 Ω/km

OHGWOutside diameter7.93 mm
Direct current resistance4.7 Ω/km

External ground wireOutside diameter7.93 mm
Impedance (Zt)408 Ω
Speed of lightning wave300 m/μs

Concrete poleSpan of the pole40 m
Height12 m

Single ground rodDiameter of ground rod16 mm
Length of ground rod2.4 m
Ground resistance®1–30 Ω
Earth resistivity40 Ω·m