Research Article

Lightning Protection Improvement and Economic Evaluation of Thailand’s 24 kV Distribution Line Based on Difference in Grounding Distance of Overhead Ground Wire

Table 4

Minimum critical impulse flashover (kV) at 10 Ω ground resistance (average in Thailand).

Lightning current (kA)Grounding distance of OHGW (m)
4080120160200

30222267292292300
40268324358359360
50310377416418420