Lightning Protection Improvement and Economic Evaluation of Thailand’s 24 kV Distribution Line Based on Difference in Grounding Distance of Overhead Ground Wire

Table 5

Reduction cost (savings cost).

Grounding distance (kA) (a)P (Ip) (b)NL (flashes/100 km/year) (c)BFR (flashes/100 km/year) (d) = (b) × (c)

No G3.300.999615.25715.250
40 m29.270.724211.048
80 m12.840.942914.386
120 m9.170.974714.870
160 m7.900.982014.982
200 m7.380.984315.017

Grounding distanceOutage cost (USD/even) (e)Damage (USD)
PV of 25 years
(f) = (d) × (e)
Reduction (USD)
PV of 25 years
()
Reduction (%)

No G28,921.704,005,228.3700.00
40 m2,900,463.3011,104,765.0727.58
80 m3,776,671.06228,557.315.71
120 m3,903,712.55101,515.822.53
160 m3,933,034.9572,193.431.80
200 m3,942,202.2463,026.131.57

Outage cost per event in distribution line service area in Thailand is 28,921.70 USD/event in the year 2020 [1], where PV is the present value.