TLS-ESPRIT short-circuit distance measurements for different transition resistance values.

Transition resistance (Ω)Natural frequency principal component (Hz)Calculated ranging point (km)Error (%)

10101874.41−0.79
20101274.85−0.20
50100575.37−0.49
10099575.97+1.30