Research Article

Rotor Transverse Slots’ Influence on Negative Sequence Loss and Heat Distribution Prediction of Large Generators Based on Improved Radial Basis Function Process Neural Network

Table 7

Maximum temperature rise comparison caused by negative sequence current under three transverse slot conditions.

Structural positionTransverse slot numberNegative sequence component proportion
3%7%11%

Big tooth023.1925.2331.57
1024.3126.3633.48
2026.3928.8237.03

Slot wedge013.4515.3621.59
1014.3116.4723.16
2016.1818.8326.96

Small tooth012.3214.2420.45
1013.1915.5122.17
2015.0817.6224.74