Identification of Critical Nodes and Accident Chains of Power Systems under the Effect of Geomagnetic Storms

Table 1

GIC of substations under the action of geoelectric fields of different strengths.

NameEastward E field GIC (A)
E = 1 V/kmE = 3 V/kmE = 5 V/kmE = 9 V/km

SUB1−7.529−22.588−37.647−67.764
SUB2−7.616−22.849−38.082−68.547
SUB37.36622.09736.82966.292
SUB4−1.435−4.305−7.176−12.916
SUB5−2.006−6.017−10.027−18.049
SUB61.9675.8999.83217.698
SUB7−5.374−16.123−26.871−48.368
SUB8−5.570−16.709−27.849−50.127
SUB9−0.060−0.181−0.302−0.544
SUB103.61010.82918.04932.487
SUB112.8558.56614.27725.698
SUB12−7.893−23.679−39.464−71.036
SUB13−0.367−1.101−1.835−3.303
SUB140.0000.0000.0000.000
SUB156.39519.18431.97457.552
SUB160.4991.4972.4944.489
SUB172.3897.16611.94421.499
SUB185.43716.31127.18548.934
SUB192.1516.45410.75619.361
SUB205.18315.54825.91346.643