Optimization and Design of a Sustainable Industrial Grid System

Table 2

Percentage of allowable voltage drop by IEC 60364 : 2001.

Voltage drop pointsLighting (%)Other uses (%)

1. Public low voltage distribution system supplying LV distribution systems35
2. Private low voltage distribution system supplying LV distribution systems68

When the main wiring systems of the installation are longer than 100 m, these voltage drops may be increased by 0.005% per meter of wiring system beyond 100 m, without this supplement being greater than 0.5%.