Research Article

Optimization and Design of a Sustainable Industrial Grid System

Table 3

List of industrial loading.

Load descriptionReal power (P) KWReactive power (Q) KVARPower factorApparent power (S) KVAVoltage (V)Current (I) KADuty (%)Estimate power demand (PD) KW

Split unit air conditional50.0030.990.8558.82415.000.0810050.00
General lighting distribution board (DB)5.562.690.906.17415.000.011005.55
General power sockets33.3320.660.8539.22415.000.0510033.33
Fire water pump A85.2350.570.8699.10415.000.14108.52
Fire water pump B85.2350.570.8699.10415.000.14108.52
Fire water pump C85.2350.570.8699.10415.000.14108.52
UPS system88.8955.090.85104.58415.000.1510088.88
Process compressor A842.11477.240.87967.946600.000.08100842.10
Process compressor B842.11477.240.87967.946600.000.081084.21
Process compressor C842.11477.240.87967.946600.000.08100842.10
Recirculation pump A46.5131.260.8356.04415.000.0810046.51
Recirculation pump B46.5131.260.8356.04415.000.08104.65
Recirculation pump C46.5131.260.8356.04415.000.0810046.51
Conveyor motor A33.3325.000.8041.67415.000.0610033.33
Conveyor motor B33.3325.000.8041.67415.000.0610033.33
Conveyor motor C33.3325.000.8041.67415.000.0610033.33
Welding system A13.646.600.9015.15415.000.02506.82
Welding system B13.646.600.9015.15415.000.02506.82
Welding system C13.646.600.9015.15415.000.02506.82
HVAC100.0061.970.85117.65415.000.16100100.00
Lighting DB A22.2213.190.8625.84415.000.0410022.22
Lighting DB B22.2213.190.8625.84415.000.04102.22
Lighting DB C22.2213.190.8625.84415.000.0410022.22
Lift11.768.210.8214.35415.000.02505.88
Total (P, Q, S, I & PD)3418.651991.193957.991.722342.41