Optimal Siting of Distributed Generation Unit in Power Distribution System considering Voltage Profile and Power Losses
Table 5
Power losses of the system with induction generator at bus bar 3.
| Branch/circuit ID | Losses | KW | KVAR |
| Line 12 | 94.4 | 31.3 | Line 23 | 91.7 | 23.2 | T1 | 9.6 | 67.2 | Line 34 | 86.6 | 12.8 | T2 | 6.2 | 38.5 | T3 | 11.2 | 79.3 | T10 | 52.7 | 7.8 | Line 45 | 10.6 | 74.5 | T4 | 35.4 | 5.2 | Line 56 | 8.0 | 56.5 | T5 | 6.3 | 44.7 | T6 | 6.2 | 38.7 | T7 | 15.8 | 168.1 | Cable 11 | 40.2 | 5.9 | Cable 12 | 25.6 | 3.8 | Cable 13 | 14.3 | 2.1 | Cable 14 | 6.3 | 0.9 | Cable 15 | 1.6 | 0.2 | Total | 522.8 | 660.9 |
|
|