Numerical Study on Electromagnetic Coupled Heat Transfer and Ultrasonic Propagation in GIS Busbar Chamber

Table 3

The maximum temperature (Tmax) and electromagnetic loss (Q) in GIS chamber with different computational grids (I = 3300 A, f = 50 Hz).

GridRegionsMinimal grid size (m)Maximal grid size (m)Total grid numbersTmax (K)Q (W/m3)

Grid 1Zone 10.01180.01554688336.25201.45
Zone 20.00690.0155
Zone 30.00710.0315

Grid 2Zone 10.00870.01557204335.85202.74
Zone 20.00500.0155
Zone 30.00650.0277

Grid 3Zone 10.00540.010610064335.67203.65
Zone 20.00450.0080
Zone 30.00560.0251

Grid 4Zone 10.00440.007214894335.65203.68
Zone 20.00360.0080
Zone 30.00450.0170