Experimental Investigations of the Seismic Performance of a Base-Isolated Uninterruptible Power Supply (UPS) through Shaking Table Tests
Table 4
Fundamental frequencies at different locations of the UPS test specimens.
| Specimens | Scaling factor (%) | Fundamental frequencies (Hz) | UPS top | Control switch | Cooling system | Transformer | X-dir. | Y-dir. | X-dir. | Y-dir. | X-dir. | Y-dir. | X-dir. | Y-dir. |
| Series A | 1A-3A | Initial | 9.08 | 17.38 | 9.05 | 13.83 | 9.08 | 17.40 | 8.98 | 16.60 | 6A-8A | 100 | 8.33 | 18.25 | 8.30 | 13.48 | 8.33 | 17.63 | 8.18 | 17.18 | 10A-12A | 200 | 8.10 | 16.28 | 8.05 | 13.25 | 8.08 | 16.25 | 7.93 | 16.23 |
| Series B | 1B-3B | Initial | 4.21 | 3.41 | 4.15 | 3.41 | 4.24 | 3.41 | 4.13 | 3.39 | 6B-8B | 100 | 4.00 | 3.38 | 3.95 | 3.38 | 4.00 | 3.38 | 3.94 | 3.37 | 10B-12B | 200 | 3.53 | 3.12 | 3.61 | 3.11 | 3.53 | 3.12 | 3.41 | 3.11 |
|
|