Experimental Investigations of the Seismic Performance of a Base-Isolated Uninterruptible Power Supply (UPS) through Shaking Table Tests
Table 5
Peak accelerations of the test specimens in Series A and B at different locations.
| Specimens | Scaling factor (%) | Peak acceleration (g) | UPS top | Control switch | Cooling system | Transformer | X-dir. | Y-dir. | X-dir. | Y-dir. | X-dir. | Y-dir. | X-dir. | Y-dir. |
| Series A | 4A | 50 | 0.443 | 0.375 | 0.512 | 0.576 | 0.680 | 0.336 | 0.414 | 0.291 | 5A | 100 | 0.694 | 0.599 | 0.960 | 1.088 | 1.058 | 0.511 | 0.618 | 0.548 | 9A | 200 | 1.575 | 0.861 | 1.861 | 1.328 | 2.291 | 1.038 | 0.880 | 1.240 |
| Series B | 4B | 50 | 0.210 | 0.209 | 0.196 | 0.214 | 0.253 | 0.216 | 0.181 | 0.262 | 5B | 100 | 0.418 | 0.385 | 0.316 | 0.339 | 0.442 | 0.360 | 0.296 | 0.338 | 9B | 200 | 0.926 | 0.928 | 0.668 | 0.730 | 0.897 | 0.833 | 0.570 | 0.675 |
|
|