Research Article

Experimental Investigations of the Seismic Performance of a Base-Isolated Uninterruptible Power Supply (UPS) through Shaking Table Tests

Table 6

Peak displacement at tops and bottoms of the UPS test specimens.

SpecimensScaling factor (%)Relative displacement (mm)
TopBottom
X-dir.Y-dir.X-dir.Y-dir.

Series A4A501.050.751.040.67
5A1002.891.251.051.01
9A2008.382.551.531.43

Series B4B505.258.772.454.98
5B10020.0127.617.5517.73
9B20097.4584.6129.4547.06