Research Article

Design Change and Operational Consideration of the HVAC System during Nuclear Power Plant Decommissioning

Table 3

HVAC operation strategies for decommissioning.

SystemTransition periodDecommissioning phase

RCB HVAC and purgeNatural ventilation, intermittent purge (with recirculation operation using 2 RCFCs and recirculation fans)Recirculation operation, entire ventilation operation (continuous or intermittent purge), partial ventilation operation (portable temporary HVAC units)
FHB HVACNormal operation (same as normal operating NPP)ā€”
MCR HVACContinuously forced ventilation (using supply and exhaust fan without recirculating flow), natural ventilation, temporary HVAC unit operationā€”